Working condition and technical data
Maximum inlet air temperature:45℃
Pressure range:0.5-1.0Mpa
Pressure dew point:-20℃ ~ -40℃
Regeneration gas consumption:0
Maximum cooling water inlet temperature:38℃
Inlet oil content:≤0.1PPm
Control mode: PLC control
Power supply: AC 380V / 220 V / 50 Hz
Period: T = 8h
Design condition: inlet temperature: 38 ℃
Working pressure: 0.7MPa
Inlet cooling water temperature: 32 ℃
Suction inlet condition of blower: 35 ℃ (RH ≤ 45%)
Pressure loss: ≤ 3% of design pressure
Note: other special requirements are welcome to customize.
Characteristics of blast heat regenerative dryer
Product specifications
model |
Air capacity (Mm3/min) |
Air nozzle diameter | Heater power(KW) | Blower power(KW) | Weight of desiccant(kg) |
Equipment weight (kg) |
Equipment size (mm) |
Cooling water circulation M³/h |
SDXG-10I | 10.9 | DN50 | 8 | 1.3 | 311 | 1000 | 1500×1157×2292 | 0.6 |
SDXG-15I | 16 | DN65 | 10 | 2.2 | 486 | 1300 | 1600×1317×2395 | 1.2 |
SDXG-20I | 22 | DN65 | 12 | 2.2 | 606 | 1500 | 1700×1379×2435 | 1.2 |
SDXG-25I | 26.8 | DN80 | 15 | 5.5 | 716 | 2000 | 1800×1475×2520 | 1.6 |
SDXG-30I | 32 | DN80 | 18 | 5.5 | 860 | 2200 | 1800×1562×2544 | 2.2 |
SDXG-40I | 43.5 | DN100 | 22 | 7.5 | 1158 | 2300 | 2000×1718×2640 | 3.3 |
SDXG-50I | 53 | DN100 | 27 | 7.5 | 1422 | 3000 | 2100×1819×2272 | 3.3 |
SDXG-60I | 67 | DN125 | 36 | 9 | 1608 | 4200 | 2418×1970×2825 | 5.5 |
SDXG-80I | 90 | DN125 | 42 | 9 | 2436 | 5400 | 2724×2146×2940 | 5.5 |
SDXG-100I | 110 | DN150 | 54 | 13 | 2926 | 6100 | 2810×2158×3068 | 9 |
SDXG-120I | 130 | DN150 | 72 | 13 | 3476 | 8100 | 2998×2363×3140 | 9 |
SDXG-150I | 160 | DN200 | 84 | 13 | 4710 | 11600 | 3480×2581×3406 | 9 |
SDXG-200I | 210 | DN200 | 96 | 18.5 | 7008 | 16000 | 4700×2578×3532 | 16 |
Optional Accessories